Abstract Header
The Effect of Dissolved Air on the Cooling Performance of a Partially-Confined FC-72 Spray
Author Info
Puterbaugh, Rebekah Lee
Permalink:
http://rave.ohiolink.edu/etdc/view?acc_num=wright1219841299
Abstract Details
Year and Degree
2008, Master of Science in Engineering (MSEgr), Wright State University, Mechanical Engineering.
Abstract
The objective of this thesis is to investigate the heat transfer performance of a partially-confined FC-72 spray with varying dissolved air concentrations. An experimental test rig consisting of a spray chamber coupled to a fluid delivery loop system was used to obtain temperature, pressure, and critical heat flux (CHF) data. A downward facing nozzle within the spray chamber allowed the FC-72 fluid to be sprayed onto an upward facing, thick-film, resistor heater. The heater was mounted onto a glass post, with a sump system to allow removal of excess fluid. Type-E thermocouples were imbedded in the post to obtain temperature data. The parametric ranges for experimental testing were as follows: volume-percent concentration of dissolved air, 5 ≤ C
m
≤ 18%, chamber pressure, 6.90×10
4
≤ P
ch
≤ 8.27×10
4
N/m
2
(10 ≤ P
ch
≤ 12 psia), subcooling, 2 ≤ ΔT
sc
≤ 12°C, volumetric flow rate, 6.31 ≤ V̇ ≤ 10.5 cm
3
/s (6.0 ≤ V̇ ≤ 10.0 gph). Test data were obtained for comparison of CHF with varying C while controlling the spray chamber pressure. No significant variation in heat transfer performance was observed. The applicability of Henry's law to the current system was investigated, and air concentration measurements using Henry's law were compared with those obtained using a direct sample method. The resulting air concentration measurements did not agree. An empirical mathematical relationship allowing for determination of surface heat flux with varying flow rate was also developed. The relationship was obtained using test data at flow rates of V̇ = 6.31, 8.41, and 10.5 cm
3
/s (6.0, 8.0, and 10.0 gph), and was validated using experimental data obtained for flow rates of V̇ = 7.36 and 9.46 cm
3
/s (7.0 and 9.0 gph).
Committee
Scott Thomas, PhD (Advisor)
James Menart, PhD (Committee Member)
J. Mitch Wolff, PhD (Committee Member)
Kirk Yerkes, PhD (Committee Member)
Pages
108 p.
Keywords
FC-72
;
ref
;
heater
;
CHF
;
Bias Er
;
¿¿¿¿¿Tsc
Recommended Citations
Refworks
EndNote
RIS
Mendeley
Citations
Puterbaugh, R. L. (2008).
The Effect of Dissolved Air on the Cooling Performance of a Partially-Confined FC-72 Spray
[Master's thesis, Wright State University]. OhioLINK Electronic Theses and Dissertations Center. http://rave.ohiolink.edu/etdc/view?acc_num=wright1219841299
APA Style (7th edition)
Puterbaugh, Rebekah.
The Effect of Dissolved Air on the Cooling Performance of a Partially-Confined FC-72 Spray.
2008. Wright State University, Master's thesis.
OhioLINK Electronic Theses and Dissertations Center
, http://rave.ohiolink.edu/etdc/view?acc_num=wright1219841299.
MLA Style (8th edition)
Puterbaugh, Rebekah. "The Effect of Dissolved Air on the Cooling Performance of a Partially-Confined FC-72 Spray." Master's thesis, Wright State University, 2008. http://rave.ohiolink.edu/etdc/view?acc_num=wright1219841299
Chicago Manual of Style (17th edition)
Abstract Footer
Document number:
wright1219841299
Download Count:
548
Copyright Info
© 2008, all rights reserved.
This open access ETD is published by Wright State University and OhioLINK.